Product Details
Natural gas solenoid valve
MVD/5
Technical Description
The MVD/5 series safety solenoid valves are single-stage automatic shut-off valves that meet the requirements of EN 161 for gas burners and gas equipment.
- Reliable function, rugged and mainte nance-free
- On request, design without non-ferrous metals
MVD/5
Natural gas solenoid valve, normally when closed, fast opening, fast closing, manual limitation of flowing gas volume by adjusting main volume.
Specifications |
Nominal diameters
Pipe thread as per ISO 7/1, Rp
Flange |
DN20
Rp3/4
Connection flange (PN 16) as per DIN EN 1092-1 |
Max. operating pressure |
Up to 360 mbar (36 kPa) or up to 500 mbar (50 kPa) - refer to type overview |
Solenoid valve |
Valve as per EN 161, Class A, Group 2, single-stage mode |
Closing time |
< 1 s |
Opening time |
< 1 s |
Fast stroke |
Adjustable |
Main volume adjustment |
Manually adjustable on MVD |
Materials of gas-conveying parts |
Housing: aluminium, steel, brass
Seals: NBR basis |
Voltage/frequency |
230 V AC (+10 % -15 %); 50-60 Hz - other voltages on request
Solenoids 60E, 61E in 24-28 VDC
External activation of solenoid coils required, see operating and mounting instructions |
Rating / power consumption |
Refer to type overview |
Switch-on duration |
100 % |
Degree of protection |
IP 54, IP 65 on request |
Switching rate |
MVD…/5: max. 1000/h
|
Measuring/ignition gas connection |
G 1/4 ISO 118, on both sides in inlet section, additionally G 3/4 on input side, form size DN 40 (flange) upwards |
Dirt trap |
Sieve installed, mesh width 1 mm |
Ambient temperature |
-15 ° C to +60 °C |
Installation position |
Solenoid from vertically upright to horizontally lying |
Closed position signal contact |
MVD/5 Type K01/1, DIN-tested, mountable on DN 10 - DN 150 |
Valve proving system |
Type VDK 200 A S02, mountable via G 1/4 test connection, Type VPS 504, mountable with adapter up to DN 80 |
Type |
pmax. |
DN / Rp |
Solenoid-No. |
Pmax.
[VA] |
I max.
~ (AC)
230 V |
Opening time |
Dimensions
[mm] |
Weight
[kg] |
øa |
b |
c |
d |
e |
f |
MVD 207/5 |
360 |
Rp 3/4 |
200 |
30 |
0,15 |
< 1 s |
75 |
100 |
135 |
85 |
160 |
200 |
2,40 |
MVD 207/5
Setting the main flow
Precautions for installation
1. The valve installation unit shall have the corresponding qualification and install according to the relevant gas pipeline construction specifications.
2. The valve should be installed in the indoor after the total intake valve, so that maintenance.
3. Should be installed according to the air flow direction indicated by the valve body, the valve body coil shall not be inverted, allowing horizontal and vertical installation.
4. The solenoid valve control line should be correctly and reliably connected, the control line is polar: the white line is positive, the black line is negative, can not be connected.
5. When the pipe is purged, it is recommended that the solenoid valve be isolated to avoid damage to the valve sealing material by debris in the pipe.
6. Before the pipeline pressure test to detect the sealing performance, the solenoid valve should be opened.
7. When opening the valve manually, it should be operated when the pressure of the inlet and outlet of the valve is balanced.
8. When the electric valve is closed, avoid connecting the wrong power supply, such as: connecting the wrong polarity, adding the wrong voltage or powering for a long time, so as not to damage the electromagnetic coil.
We reserve the right to make any changes in the interest of technical progress.